Completely Self-Protected Transformers (CSP) offer a complete and safe solution against lightning, switch surges and severe overloads.
Technical specification
- GENERAL TECHNICAL INFORMATION
- Power Range kVA: 3. 5, 10, 15, 25, 37, 50, 75, 100, 167, 250, 333, 500
- Temperature Rise: 55°C or 65°C
- Cooling type : ONAN, OA,
- Frequency: 50Hz or 60Hz
- Polarity : Additive or Subtractive
- Primary Voltage : 2400V through 34500 GrdY / 19920V
- Secondary Voltage : 120 / 240V, 240 / 480 V, 277V, 600V
- Insulation Class : 2.4Kv~34.5kV (150kV BIL) and below
- Taps: none, or as an option, 4 x 2,5% HV
- HV Bushings: cover and sidewall mounted available
- STANDARD FEATURES
- −−Core and coils designed for an optimum Total Ownership Cost (TOC)
- −−Wound core with step-lap joints for increased efficiency and lower noise levels
- −−“Low-high-low” windings for increased short circuit strength, efficiency and thermal strength
- −−“Low-high-low” windings for increased short circuit strength, efficiency and thermal strength
- −−Computer aided design for mechanical & electrical calculations (C.A.D.)
- −−Paint system meeting or exceeding the performance of the IEEE C57.12.28 Standard
- −−Lifting lugs meeting all of the requirements of the CSA C2.1-06 and CSA C2.2-06 Standard
- −−Multiple cover clamps to ensure proper sealing and to mini-mize water retention on the cover edge
- −−Cover or sidewall mounted high voltage bushing(s) as required
- −−Low voltage spade or clamp type (basket) terminals as required
- −−Provision for surge arrester bracket, bracket available as an option
- −−Automatic self-resealing pressure relief valve
- OPTIONAL PRODUCT ACCESSORIES
- Cold-Rolled Grain Oriented Silicon Steel Core (CRGO) or Amorphous Metal Core (AMDT)
- Stainless Steel Tanks and Cover
- Extra Creep Bushing
- Surge Arrester Bracket
- The CSP protection package consists of four related components: H.V Fuse Link, Secondary Breaker, Signal light, External Surge Arrester that work together to provide complete self-contained protection against surge currents, short circuits and overloads.
- Units can be customized to specific requirements
Standards
IEEE C57.12.00,
ANSI C 57.12.20
IEC 60076
Certificate
ISO 9001
ISO 14001
Features and benefits
• High voltage surge arrester
• Primary protective link.
• Secondary circuit breaker
• Secondary breaker operating handle with emergency overload reset and overload signal light.
• 18 months standard warranty
• After sales maintenance and spare parts service
Option: Amorphous Metal Core
Product Overview
Learn More...
BIL95KV Single Phase Pole Mounted Transformer
pole-mounted Conventional type transformer 7200/12470Y, 7620/13200Y, 8320/14400Y
BIL95KV Single Phase Pole Mounted Transformer
DownloadSingle Phase CSP and CP Transformers
csp transformer, pole type transformer, overhead transformer, ansi transformer,single-phase, pole-type,kva transformers
Single Phase CSP and CP Transformers
11KV IEC pole mounted transformers
11kv transformer,iec single-phase transformer, pole-mounted transformer